Development of deflector flat spray nozzle with mixed of water and organic citric acid for emissions trap and cooling in the kitchen hood ventilation system
The growth of food industry is rapidly-evolving due to the increase of human population, which results in changes to the cooking technology development. This condition leads to increased pollution rate, especially air and water pollution. Recently, several technologies and research are developed...
Saved in:
Main Author: | |
---|---|
Format: | Thesis |
Language: | English English English |
Published: |
2018
|
Subjects: | |
Online Access: | http://eprints.uthm.edu.my/208/1/24p%20MOHAMAD%20FARID%20SEIS.pdf http://eprints.uthm.edu.my/208/2/MOHAMAD%20FARID%20SEIS%20COPYRIGHT%20DECLARATION.pdf http://eprints.uthm.edu.my/208/3/MOHAMAD%20FARID%20SEIS%20WATERMARK.pdf http://eprints.uthm.edu.my/208/ |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The growth of food industry is rapidly-evolving due to the increase of human
population, which results in changes to the cooking technology development. This
condition leads to increased pollution rate, especially air and water pollution.
Recently, several technologies and research are developed to improve the
commercial kitchen industry, especially in hotels and restaurants. The function of
kitchen hood is to remove gas, odour, heat and steam during cooking process. The
main purpose of this study is to introduce mist spray (atomization) to replace the
water spray system in the existing kitchen hood. In addition, this study compared the
existing (conventional) nozzles in the market such as KSJB model (water spray) and
AL75 model (mist spray). Then, this study compared two nozzle designs of deflector
nozzles that is ND2.5 A1.0 and ND2.5 B1.0. The difference between these two
nozzles is the swirl angle. The swirl angles for ND2.5 A1.0 and ND2.5 B1.0 are 10o
and 15o respectively. The use of the new nozzles is to reduce water consumption in
the kitchen hood ventilation system. The other function is to introduce organic citric
acid as an agent to absorb gas emitted during cooking, besides looking at the effect
of nozzle design in limiting gas emission and reducing kitchen hood temperature
during cooking. Several methods were used in this study, such as the development of
a small size kitchen hood with one nozzle using water sensitive paper (WSP) to spray
droplets with fluid pressure from one to six bar, using a gas analyzer for gas reading
and thermocouple for temperature reading in the kitchen hood system. The results
obtained from the comparison between KSJB model and AL75 model showed that
the mist spray nozzle (AL75) is better than the water spray (KSJB) model. On
average, the difference in gas emission percentage between AL75 and KSJB is 15.08
– 35.82 % while the difference in temperature is 2.98 – 11.35 %. Then, the
comparison between the new nozzles shows that ND2.5 A1.0 is better than ND
2.5B1.0. On average, the difference in gas emission percentage between ND2.5 A1.0
and ND 2.5B1.0 is 2.65 – 24.32 % while the difference in temperature is 6.48 –
14.86 %. Lastly, comparison between AL75 and the new model which is ND2.5
A1.0 shows that ND2.5 A1.0 has better performance than AL75. On average, the
difference in gas emission percentage between these two models is 13.12 – 33 %
while the difference in temperature is 11.84 – 20.22 %. However, the AL75 nozzle
can reduce water consumption by 60 – 80 % as compared to KSJB, depending on air
pressure. The results show that the atomization nozzles (AL75, ND2.5 A1.0 and
ND2.5 B1.0) have better effect than the water spray (KSJB) nozzle. The factors that
improves kitchen hood performance are high spray angle, large droplet size and the
usage of organic citric acid. In addition, mist spray can reduce water consumption
and water pollution. In fact, the use of organic citric acid can reduce air pollution in
the cooking process. For future studies, it is suggested to use an actual kitchen hood
size for testing and the quantity for each nozzle type is increased in the kitchen hood
system. |
---|