Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

This paper studies an application of wye- zigzag transformes for reducing harmonics in the neutral conductors of a three phase 415/240V distribution system. Triplen harmonic currents add up in the neutral conductor of the distribution system feeding the non linear loads such as personal computers...

Full description

Saved in:
Bibliographic Details
Main Authors: Omar , Rosli, Ahmad, Azhar, Sulaiman , Marizan
Format: Article
Language:English
Published: jeteas.scholarlinkresearch.org 2010
Subjects:
Online Access:http://eprints.utem.edu.my/id/eprint/9092/1/marizan%236.pdf
http://eprints.utem.edu.my/id/eprint/9092/
http://jeteas.scholarlinkresearch.org/articles/TRIPLEN%20HARMONIC%20MITIGATION.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper studies an application of wye- zigzag transformes for reducing harmonics in the neutral conductors of a three phase 415/240V distribution system. Triplen harmonic currents add up in the neutral conductor of the distribution system feeding the non linear loads such as personal computers and electronic office machines with switch mode power supplies. The zigzag transformer is installed between the distribution panel and the high harmonics producing loads. This research makes use of a star-zigzag grounded transformer.