A grid-connected optimal hybrid PV-BES System sizing for Malaysian Commercial Buildings

In this article, the optimal sizing of hybrid solar photovoltaic and battery energy storage systems is evaluated with respect to rooftop space and feed-in tariff rates. The battery scheduling is performed using a proposed rule-based energy management strategy. The rules are formulated based on the d...

Full description

Saved in:
Bibliographic Details
Main Authors: Hossain, Jahangir, Saeed, Nagham, Abdul Kadir, Aida Fazliana, Shareef, Hussain, Manojkumar, Rampelli, Hanafi, Ainain Nur
Format: Article
Language:English
Published: MDPI AG 2023
Online Access:http://eprints.utem.edu.my/id/eprint/27494/2/0033429072023269.PDF
http://eprints.utem.edu.my/id/eprint/27494/
https://www.mdpi.com/2071-1050/15/13/10564
https://doi.org/10.3390/su151310564
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In this article, the optimal sizing of hybrid solar photovoltaic and battery energy storage systems is evaluated with respect to rooftop space and feed-in tariff rates. The battery scheduling is performed using a proposed rule-based energy management strategy. The rules are formulated based on the demand limit, PV export power limit, and state of charge of the battery. Furthermore, optimization modeling with initial choices of parameters and constraints in terms of solar photovoltaic and battery energy storage capabilities is developed to minimize the total net present cost. The hourly values of solar irradiance, air temperature, electrical loads, and electricity rates are considered the inputs of the optimization process. The optimization results are achieved using particle swarm optimization and validated through an uncertainty analysis. It is observed that an optimal photovoltaic and battery energy storage system can reduce the cost of electricity by 12.33%, including the sale of 5944.029 kWh of electricity to the grid. Furthermore, energy consumption, peak demand, and greenhouse gas emissions are reduced by 13.71%, 5.85%, and 62.59%, respectively. A comprehensive analysis between the variable and fixed data for the load, energy from PV, batteries, and the grid, and costs demonstrates that the optimal sizing of photovoltaic and battery energy storage systems with the best mix of energy from PV, batteries, and the grid provides the optimal solution for the proposed configuration.