Considering the effects of a cross-arm on a contaminated polymer insulator at different angles
This paper considers the effects of a cross-arm on a contaminated polymer insulator at different angles (90°, 60° and 45°) with negative and positive impulses. An experiment was conducted using a 10 kV polymer insulator that was contaminated with 4 % salt (a mixture of distilled water and sodium chl...
Saved in:
Main Authors: | , , , , , |
---|---|
Format: | Conference or Workshop Item |
Language: | English |
Published: |
IEEE
2015
|
Online Access: | http://psasir.upm.edu.my/id/eprint/47635/1/Considering%20the%20effects%20of%20a%20cross-arm%20on%20a%20contaminated%20polymer%20insulator%20at%20different%20angles.pdf http://psasir.upm.edu.my/id/eprint/47635/ |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
id |
my.upm.eprints.47635 |
---|---|
record_format |
eprints |
spelling |
my.upm.eprints.476352019-04-16T07:20:00Z http://psasir.upm.edu.my/id/eprint/47635/ Considering the effects of a cross-arm on a contaminated polymer insulator at different angles Jamaludin, Farah Adilah Abd Rahman, Muhammad Syahmi Izadi, Mahdi Ab Kadir, Mohd Zainal Abidin Azis, Norhafiz Jasni, Jasronita This paper considers the effects of a cross-arm on a contaminated polymer insulator at different angles (90°, 60° and 45°) with negative and positive impulses. An experiment was conducted using a 10 kV polymer insulator that was contaminated with 4 % salt (a mixture of distilled water and sodium chloride). From the experiment, the behaviour of the voltage breakdown and leakage current of the contaminated insulator positioned at different angles from the cross-arm was evaluated under different impulse polarities. The results show that the values of the breakdown voltage and leakage current decrease with angle when using the 90° angle as a reference. The reason for this study into the effects of the cross-arm on a contaminated polymer insulator is because in the real case, when the insulators are installed on an angle tower, the forces or tensions due to the weather conditions (especially under strong winds) and from the distribution lines themselves will force the installed insulators to be tilted from its original 90° angle position. IEEE 2015 Conference or Workshop Item PeerReviewed application/pdf en http://psasir.upm.edu.my/id/eprint/47635/1/Considering%20the%20effects%20of%20a%20cross-arm%20on%20a%20contaminated%20polymer%20insulator%20at%20different%20angles.pdf Jamaludin, Farah Adilah and Abd Rahman, Muhammad Syahmi and Izadi, Mahdi and Ab Kadir, Mohd Zainal Abidin and Azis, Norhafiz and Jasni, Jasronita (2015) Considering the effects of a cross-arm on a contaminated polymer insulator at different angles. In: 2015 IEEE Conference on Energy Conversion (CENCON), 19-20 Oct. 2015, Johor Bahru, Malaysia. (pp. 263-267). 10.1109/CENCON.2015.7409551 |
institution |
Universiti Putra Malaysia |
building |
UPM Library |
collection |
Institutional Repository |
continent |
Asia |
country |
Malaysia |
content_provider |
Universiti Putra Malaysia |
content_source |
UPM Institutional Repository |
url_provider |
http://psasir.upm.edu.my/ |
language |
English |
description |
This paper considers the effects of a cross-arm on a contaminated polymer insulator at different angles (90°, 60° and 45°) with negative and positive impulses. An experiment was conducted using a 10 kV polymer insulator that was contaminated with 4 % salt (a mixture of distilled water and sodium chloride). From the experiment, the behaviour of the voltage breakdown and leakage current of the contaminated insulator positioned at different angles from the cross-arm was evaluated under different impulse polarities. The results show that the values of the breakdown voltage and leakage current decrease with angle when using the 90° angle as a reference. The reason for this study into the effects of the cross-arm on a contaminated polymer insulator is because in the real case, when the insulators are installed on an angle tower, the forces or tensions due to the weather conditions (especially under strong winds) and from the distribution lines themselves will force the installed insulators to be tilted from its original 90° angle position. |
format |
Conference or Workshop Item |
author |
Jamaludin, Farah Adilah Abd Rahman, Muhammad Syahmi Izadi, Mahdi Ab Kadir, Mohd Zainal Abidin Azis, Norhafiz Jasni, Jasronita |
spellingShingle |
Jamaludin, Farah Adilah Abd Rahman, Muhammad Syahmi Izadi, Mahdi Ab Kadir, Mohd Zainal Abidin Azis, Norhafiz Jasni, Jasronita Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
author_facet |
Jamaludin, Farah Adilah Abd Rahman, Muhammad Syahmi Izadi, Mahdi Ab Kadir, Mohd Zainal Abidin Azis, Norhafiz Jasni, Jasronita |
author_sort |
Jamaludin, Farah Adilah |
title |
Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
title_short |
Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
title_full |
Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
title_fullStr |
Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
title_full_unstemmed |
Considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
title_sort |
considering the effects of a cross-arm on a contaminated polymer insulator at different angles |
publisher |
IEEE |
publishDate |
2015 |
url |
http://psasir.upm.edu.my/id/eprint/47635/1/Considering%20the%20effects%20of%20a%20cross-arm%20on%20a%20contaminated%20polymer%20insulator%20at%20different%20angles.pdf http://psasir.upm.edu.my/id/eprint/47635/ |
_version_ |
1643833937111285760 |
score |
13.211869 |