Probabilistic approach in sizing distribution transformers
This paper presents a probabilistic approach in sizing distribution transformers capacity supplying residential, commercial, and combination of residential and commercial loads. Load data recorded from the three categories of aggregate loads are used to establish probability distribution curves base...
Saved in:
Main Authors: | , |
---|---|
Other Authors: | |
Format: | Conference paper |
Published: |
2023
|
Subjects: | |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper presents a probabilistic approach in sizing distribution transformers capacity supplying residential, commercial, and combination of residential and commercial loads. Load data recorded from the three categories of aggregate loads are used to establish probability distribution curves based on the goodness-of-fit test. The gamma distribution is found to be the best fit among all probability distributions for kilo-volt-ampere (KVA) recorded at peak periods. It is shown that distribution transformers capacity could be more optimally sized by considering a risk factor and thus results in cost savings. �2010 IEEE. |
---|