An Experimental Study of Heat Transfer and Friction Factor Characteristics of Finned Flat Tube Banks with In-Line Tubes Configurations
The experimental study has been made to investigate heat transfer and pressure drop for air flow around finned flat tube banks in-line configurations with laminar forced convection. Measurements were conducted for twelve tubes in the flow direction, four tubes in the row. Four air velocity (0.2, 0.5...
Saved in:
Main Authors: | , , |
---|---|
Format: | Article |
Language: | English |
Published: |
Trans Tech Publications, Switzerland
2014
|
Subjects: | |
Online Access: | http://umpir.ump.edu.my/id/eprint/5601/1/Tahseen-ICAM2E.pdf http://umpir.ump.edu.my/id/eprint/5601/ http://www.scientific.net/AMM.564.197 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The experimental study has been made to investigate heat transfer and pressure drop for air flow around finned flat tube banks in-line configurations with laminar forced convection. Measurements were conducted for twelve tubes in the flow direction, four tubes in the row. Four air velocity (0.2, 0.5, 0.8 and 2.0 m/s) identical to the Reynolds number, ReDh based hydraulic diameter varied 124 to
1238. The total heat flux supplies in all tubes change four times from 473.2 to 3871.7 W/m2. The study results indicate that the average heat transfer coefficient,h and the average Nusselt number. of all tubes have increased 113.6%-150.3% with ReDh numbers varying from 124 to 1238 at the fixed heat flux. Likewise, the friction factor decreases 57.7% with a ReDh number range 124-1238. |
---|