Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.]
It is well known that the internal partial discharge (PD) are small electric sparks that occurred due to defect in power cable insulation. This will be lead to premature failure of cable which consequently interrupt the supply on the distribution lines. In this paper, the results of internal partial...
Saved in:
Main Authors: | , , , , , , |
---|---|
Format: | Article |
Language: | English |
Published: |
Universiti Teknologi MARA Press (Penerbit UiTM)
2020
|
Subjects: | |
Online Access: | http://ir.uitm.edu.my/id/eprint/42390/1/42390.pdf http://ir.uitm.edu.my/id/eprint/42390/ https://jeesr.uitm.edu.my https://doi.org/10.24191/jeesr.v17i1.013 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
id |
my.uitm.ir.42390 |
---|---|
record_format |
eprints |
spelling |
my.uitm.ir.423902021-02-25T05:02:18Z http://ir.uitm.edu.my/id/eprint/42390/ Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] Rameli, Norhidayu Abd. Halim, Huzainie Shafi Nor Azli, Muhd. Irfan Anthony, Tashia Marie Pangah @ Pa’at, Mohd Azraei Ibrahim, Muhammad Faiz Nor Arifin, Nur Amira Detectors. Sensors. Sensor networks It is well known that the internal partial discharge (PD) are small electric sparks that occurred due to defect in power cable insulation. This will be lead to premature failure of cable which consequently interrupt the supply on the distribution lines. In this paper, the results of internal partial discharge detected by rogowski coil (RC) sensor were presented. The RC sensors were designed, fabricated and tested in the laboratory with varying high frequency sinusoidal and impulse signals. An artificial PD defect was also created inside a straight through joint (STJ), medium voltage aerial bundle cable (MVABC) to generate PD signals. PD testing data in the laboratory were collected and analysed. Results indicates that the RC sensors able to detects injected continuos sinusoidal signal at lower frequencies ranging from 0.5 MHz to 10 MHz. The detected PD signal generated from artificial PD defect from RC sensor were found to be slightly higher amplitude as compared to commercial PD sensor, High Frequency Current Transformer (HFCT). Thus findings shows that the RC sensor able to be used as sensor to detect the internal partial discharge at MVABC specifically at STJs. Universiti Teknologi MARA Press (Penerbit UiTM) 2020 Article PeerReviewed text en http://ir.uitm.edu.my/id/eprint/42390/1/42390.pdf Rameli, Norhidayu and Abd. Halim, Huzainie Shafi and Nor Azli, Muhd. Irfan and Anthony, Tashia Marie and Pangah @ Pa’at, Mohd Azraei and Ibrahim, Muhammad Faiz and Nor Arifin, Nur Amira (2020) Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.]. Journal of Electrical & Electronic Systems Research (JEESR), 17. pp. 95-100. ISSN 1985-5389 https://jeesr.uitm.edu.my https://doi.org/10.24191/jeesr.v17i1.013 |
institution |
Universiti Teknologi Mara |
building |
Tun Abdul Razak Library |
collection |
Institutional Repository |
continent |
Asia |
country |
Malaysia |
content_provider |
Universiti Teknologi Mara |
content_source |
UiTM Institutional Repository |
url_provider |
http://ir.uitm.edu.my/ |
language |
English |
topic |
Detectors. Sensors. Sensor networks |
spellingShingle |
Detectors. Sensors. Sensor networks Rameli, Norhidayu Abd. Halim, Huzainie Shafi Nor Azli, Muhd. Irfan Anthony, Tashia Marie Pangah @ Pa’at, Mohd Azraei Ibrahim, Muhammad Faiz Nor Arifin, Nur Amira Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
description |
It is well known that the internal partial discharge (PD) are small electric sparks that occurred due to defect in power cable insulation. This will be lead to premature failure of cable which consequently interrupt the supply on the distribution lines. In this paper, the results of internal partial discharge detected by rogowski coil (RC) sensor were presented. The RC sensors were designed, fabricated and tested in the laboratory with varying high frequency sinusoidal and impulse signals. An artificial PD defect was also created inside a straight through joint (STJ), medium voltage aerial bundle cable (MVABC) to generate PD signals. PD testing data in the laboratory were collected and analysed. Results indicates that the RC sensors able to detects injected continuos sinusoidal signal at lower frequencies ranging from 0.5 MHz to 10 MHz. The detected PD signal generated from artificial PD defect from RC sensor were found to be slightly higher amplitude as compared to commercial PD sensor, High Frequency Current Transformer (HFCT). Thus findings shows that the RC sensor able to be used as sensor to detect the internal partial discharge at MVABC specifically at STJs. |
format |
Article |
author |
Rameli, Norhidayu Abd. Halim, Huzainie Shafi Nor Azli, Muhd. Irfan Anthony, Tashia Marie Pangah @ Pa’at, Mohd Azraei Ibrahim, Muhammad Faiz Nor Arifin, Nur Amira |
author_facet |
Rameli, Norhidayu Abd. Halim, Huzainie Shafi Nor Azli, Muhd. Irfan Anthony, Tashia Marie Pangah @ Pa’at, Mohd Azraei Ibrahim, Muhammad Faiz Nor Arifin, Nur Amira |
author_sort |
Rameli, Norhidayu |
title |
Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
title_short |
Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
title_full |
Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
title_fullStr |
Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
title_full_unstemmed |
Partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / Norhidayu Rameli … [et al.] |
title_sort |
partial discharge detection using rogowski coil sensor on medium voltage aerial bundle cable / norhidayu rameli … [et al.] |
publisher |
Universiti Teknologi MARA Press (Penerbit UiTM) |
publishDate |
2020 |
url |
http://ir.uitm.edu.my/id/eprint/42390/1/42390.pdf http://ir.uitm.edu.my/id/eprint/42390/ https://jeesr.uitm.edu.my https://doi.org/10.24191/jeesr.v17i1.013 |
_version_ |
1692994695067598848 |
score |
13.211869 |