Technique for assessment of voltage stability in Ill-conditioned radial distribution network

A technique is proposed in this letter to study voltage collapse situation in a radial distribution network. The radial distribution network has been reduced to a single line equivalent circuit and then represented through a π network. A stability index is developed that indicates the severity of th...

Full description

Saved in:
Bibliographic Details
Main Authors: Moghavvemi, M., Faruque, M.O.
Format: Article
Published: IEEE, Piscataway, NJ, United States 2001
Subjects:
Online Access:http://eprints.um.edu.my/9645/
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A technique is proposed in this letter to study voltage collapse situation in a radial distribution network. The radial distribution network has been reduced to a single line equivalent circuit and then represented through a π network. A stability index is developed that indicates the severity of the loading situation of the system. The index can have a maximum value of one (1.00) when the system is at the point of collapse and a minimum value of zero (0) when there is no load in the system. Voltage collapse can be assessed based on the value of the developed index. If the system yields a value exceeding its maximum limit of stability index (1.00) it indicates voltage collapse situation. The proposed technique is tested on a practical system of 12-bus radial system (main feeders only) and on a 27-bus radial distribution system with laterals. The results obtained are encouraging and indicate that the technique has the potential to be used as a tool for system monitoring and future load planning.