Correction of under-reaching in twin circuit parallel overhead lines without residual current input from the parallel line

Mutual coupling poses one of the most difficult problems witnessed during single phase to earth fault, in transmission line protection. In lines, on multiple circuit towers or on the same right of way, the zero-sequence circuits of the lines get mutually coupled causing an error in the apparent impe...

全面介紹

Saved in:
書目詳細資料
Main Authors: Bin Abdullah M.F., Mukerjee R.N., Ramachandaramurthy V.K.
其他作者: 57188825497
格式: Conference paper
出版: Institute of Electrical and Electronics Engineers Inc. 2023
主題:
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!

相似書籍